INSTALLATION INSTRUCTIONS62-0331-11JADE™ Economizer Module(MODEL W7220)This document describes wiring, power up, basic troubleshooting, and common ins
JADE™ ECONOMIZER MODULE62-0331—11 10Using the Keypad with Settings and ParametersTo use the keypad when working with Setpoints, System and Advanced Se
JADE™ ECONOMIZER MODULE11 62-0331—11STATUS CONTINUEDCOOL Y2-IN OFF ON/OFF Y2-I signal from space thermostat or unitary controller for second stage coo
JADE™ ECONOMIZER MODULE62-0331—11 12SETPOINTS MAT SET 53ºF 38 to 70 ºF; increment by 1The economizer will modulate the OA damper to maintain the mixed
JADE™ ECONOMIZER MODULE13 62-0331—11SYSTEM SETUPINSTALL 01/01/11 Display order = MM/DD/YYSetting order = DD, MM, then YY.UNITS DEG ºF ºF or ºC Sets ec
JADE™ ECONOMIZER MODULE62-0331—11 14ADVANCED SETUPMA LO SET 45ºF 35 to 55 ºF;increment by 1ºTemp to activate Freeze Protection (close damper or modula
JADE™ ECONOMIZER MODULE15 62-0331—11CHECKOUTfDAMPER VMIN-HS n/a n/a Positions damper to VMIN position.DAMPER VMAX-HS (LS) n/a n/a Positions damper to
JADE™ ECONOMIZER MODULE62-0331—11 16SEQUENCE OF OPERATIONTable 5. Dry Bulb Operation No DCV (CO2 sensor) - 1 Speed Fan.aWith stage 3 delay (STG3 DLY)
JADE™ ECONOMIZER MODULE17 62-0331—11Table 7. Enthalpy Operation No DCV (CO2 sensor) - 1 Speed Fan.aWith stage 3 delay (STG3 DLY) in Advanced setup men
JADE™ ECONOMIZER MODULE62-0331—11 18Table 10. Dry Bulb Operation With DCV (CO2 sensor) - 2 Speed Fan.aWith stage 3 delay (STG3 DLY) in Advanced setup
JADE™ ECONOMIZER MODULE19 62-0331—11Table 12. Enthalpy Operation With DCV (CO2 sensor) - 2 Speed Fan.aWith stage 3 delay (STG3 DLY) in Advanced setup
JADE™ ECONOMIZER MODULE62-0331—11 2INSTALLATION AND SETUPThe Economizer module may be mounted in any orientation. However, mounting in the orientation
JADE™ ECONOMIZER MODULEAutomation and Control SolutionsHoneywell International Inc.1985 Douglas Drive NorthGolden Valley, MN 55422customer.honeywell.
JADE™ ECONOMIZER MODULE3 62-0331—11Fig. 1. Stand-alone dry bulb Economizer configuration with black motor M7215. ROOF TOP UNITY1OY2OY1IY2IOCC24 VAC1K1
JADE™ ECONOMIZER MODULE62-0331—11 4Fig. 2. Stand-alone dry-bulb Economizer configuration with Honeywell MS7403 Direct Coupled Actuator.ROOF TOP UNITY1
JADE™ ECONOMIZER MODULE5 62-0331—11Fig. 3. Stand-alone dry-bulb Economizer configuration with Honeywell MS3103J or MS3105J communicating actuators.ROO
JADE™ ECONOMIZER MODULE62-0331—11 6Fig. 4. Economizer with Sylk Bus sensors for enthalpy configuration with Honeywell M7215 black motor.S-BUSS-BUSOUTS
JADE™ ECONOMIZER MODULE7 62-0331—11Fig. 5. Economizer with Sylk Bus sensors for enthalpy configuration with a Honeywell MS7505 or MS7503 Direct Couple
JADE™ ECONOMIZER MODULE62-0331—11 8Fig. 6. Economizer with Sylk bus sensor for enthalpy configuration with Honeywell MS3103 or MS3105 communicating ac
JADE™ ECONOMIZER MODULE9 62-0331—11Fig. 8. Single Enthalpy curves and boundaries. Power UpAfter the module is mounted and wired, apply power.Power Up